Brand Name : JUGE

Model Number : AG600

Certification : IOS9001, CE

Place of Origin : Nanjing, China

MOQ : 1 Unit

Price : USD100-1000

Payment Terms : T/T,Online Order

Supply Ability : 100 Unit/Week

Delivery Time : 10-15 working days

Packaging Details : Neutral carton

Name : Gas Detector

Detect Gas : HCL

Unit : PPM, %LEL, %VOL, mg/m³

‌Detection Principle‌ : Electrochemical, Infrared, PID etc..

Range : 0-100%LEL/PPM/%VOL

Contact Now

HCl Gas Detector Fixed Hydrogen Chloride Corrosive Gas Leak Alarm Industrial Safety System Honeywell Sensor

>>Overview

Our company's online gas detector utilizes original imported smart gas sensors, serving as an intelligent, high-performance instrument capable of continuous online monitoring of combustible gases, toxic/hazardous gases, and specialty gases.
Featuring an integrated flameproof enclosure structure, the detector delivers high sensitivity and precision. Through connection to a GDS gas alarm controller and monitoring management software, it enables real-time concentration display on computers. Additionally, by incorporating an optional wireless module, real-time monitoring data and alarm status can be transmitted to safety control centers.


>>Features
◆ ‌Original imported high-performance sensors‌ ensure high measurement accuracy, excellent repeatability, and extended service life.
◆ ‌Independent AD chip‌ effectively resists electromagnetic interference and filters disruptive wavelengths.
◆ Instrument supports ‌dual displays (LED digital tube & LCD)‌, compliant with the latest national standards.
◆ Multiple selectable units: ‌mg/m³, ppm, VOL%, LEL%‌, etc.
◆ ‌AI-based temperature/humidity compensation algorithm‌ minimizes measurement errors.
◆ ‌Automatic protection‌ against high-concentration gas impact; features ‌factory reset function‌ to prevent misoperation.
◆ ‌Infrared remote control‌ enables operation without opening the enclosure – simple and convenient.
◆ Configurable outputs: ‌3-wire 4-20mA‌, ‌RS485‌, relay contacts; supports ‌HART protocol‌.
◆ ‌IP66 protection rating‌ for harsh industrial environments.
◆ ‌Triple explosion-proof certification‌ (Ex db ib IIC T6 Gb / Ex ib tb IIIC T80°C Db) – Certified by National Explosion-proof Electrical Testing Center.



>>Main technical parameters

Detection Principle Constant potential electrolysis, NDIR infrared optics, Catalytic combustion, PID photoionization, Laser TDLAS
Measuring Range 0-10, 0-100, 0-1000 (Customizable range)
Unit PPM, mg/m³, LEL%, VOL%, etc.
Resolution

0.1,0.01,0.001

Sampling Method

Free diffusion type – Online continuous detection with free diffusion method.

Installation Method

Wall-mounted; Pipeline-mounted (clamp-on or insertion type, with external threads)

Indication Error ≤±3% F.S
Repeatability ±2% (F.S/year)
Zero Drift ±1% (F.S/year)
Response Time

20 seconds (T90) (higher requirements depend on sensor performance)

Recovery Time

10 seconds (T90) (higher requirements depend on sensor performance)

Power Supply 12-36 VDC
Power Consumption

2.5 W (at DC24V)

Environmental Pressure

80 kPa ~ 120 kPa

Environmental Temperature

-30℃~+50℃ (Typical), -40℃~+80℃ (Limit)
(For higher temp/humidity environments, our pre-conditioning gas monitoring system is available)

Environmental Humidity

10%~95% RH (non-condensing)

Main Material

① Housing: ADC12 aluminum alloy with Teflon paint finish, wear/corrosion-resistant (316L stainless steel housing optional for harsh environments)

②Gas Chamber: High-strength, wear/corrosion-resistant aluminum profile; External thread M351.5

Output Signal

① 3-wire 4-20mA current output (compatible with controllers, PLC, DCS)

② RS-485 digital output

③ 2 relay alarm outputs (high/low segments): Passive contact, 30V 1A / 125VAC 0.5A
④ HART output (Optional, configurable)

Signal Transmission

Shielded three-core (or four-core) cable; maximum transmission distance: 1000-2000 meters

Alarm Method

Audible and visual alarm (optional, alarm sound <90 dB)

Direct Reading

Measured value, max/min values

Data Download

RS485 serial port for data export

Calibration

2-4 point calibration; customizable calibration values

Explosion-proof Electrical


① M20 internal thread (Optional: 1/2"NPT, G3/4, G1/2 internal threads)

② Explosion-proof cable gland (Optional, certified)


Explosion-proof Mark

Ex db ib IIC T6 Gb,Ex ib tb IIIC T80°C Db

Protection Level

IP66

Dimensions

180 mm (H) × 140 mm (W) × 92 mm (D)

Weight

Approx. 1.6 kg (aluminum alloy housing)

Compliance Standards

GB15322.1-2003, GB3836.1-2010, GB3836.2-2010

Quality Assurance

1-year warranty; free repair during warranty period



>>List of Commonly Detected Gas Types

NO

Detection

Range

Accuracy

T90 Response time

Resolution

Alarm set point (low/high)

1

PH3

0 – 5 ppm

±5% (F.S)

≤ 25 s

0.01 ppm

0.3 ppm/5 ppm

2

O2

0-30%Vol

±5% (F.S)

≤ 15 s

0.10% Vol

18.0%Vol/23.0%Vol

3

EX

0-100% LEL

±5% (F.S)

≤ 15 s

1% LEL

25.0%/50.0% LEL

4

CO

0 - 2000 ppm

±5% (F.S)

≤ 25 s

1 ppm

50 ppm/100 ppm

5

H2S

0 -100 ppm

±5% (F.S)

≤ 30 s

1 ppm

10 ppm/20 ppm

6

SO2

0 - 100 ppm

±5% (F.S)

≤ 30 s

0.1 ppm

2 ppm /10 ppm

7

CI2

0 - 20 ppm

±5% (F.S)

≤ 30 s

0.1 ppm

1 ppm /10 ppm

8

NH3

0 – 200 ppm

±5% (F.S)

≤ 50 s

1 ppm

25 ppm /50 ppm

9

NO2

0 - 20 ppm

±5% (F.S)

≤ 25 s

0.1 ppm

3 ppm/10 ppm

10

NO

0 - 250 ppm

±5% (F.S)

≤ 60 s

1 ppm

25 ppm/50 ppm

11

H2

0 - 1000 ppm

±5% (F.S)

≤ 60 s

1 ppm

50 ppm /100 ppm

12

HCN

0 - 50 ppm

±5% (F.S)

≤ 200 s

0.1 ppm

10 ppm /20 ppm

13

HCL

0 - 20 ppm

±5% (F.S)

≤ 60 s

0.1 ppm

5 ppm /10 ppm

14

CH4

0 - 5% Vol

±5% (F.S)

≤ 60 s

0.1% Vol

customized

15

CO2

0 - 5% Vol (0-5000ppm)

±5% (F.S)

≤ 60 s

0.01% Vol (1 ppm)

customized

16

PID(VOCs)

1-1999 ppm

±5% (F.S)

≤ 20 s

0.1 ppm

customized

17

C3H8

0 - 5%Vol

±5% (F.S)

≤ 60s

0.01% Vol

customize

18

O3

0 – 5 ppm

±5% (F.S)

≤ 30s

0.02 ppm

1ppm/2 ppm

19

SF6

0 – 1000 ppm

±5% (F.S)

≤ 60s

0.2ppm

25ppm/50 ppm

20

HF

0 – 10 ppm

±5% (F.S)

≤ 60s

0.1ppm

3ppm/10 ppm


Remark: Customized alarm setting points and detection ranges are also available.


Wholesale HCl Gas Detector Fixed Hydrogen Chloride Corrosive Gas Leak Alarm Industrial Safety System Honeywell Sensor from china suppliers

HCl Gas Detector Fixed Hydrogen Chloride Corrosive Gas Leak Alarm Industrial Safety System Honeywell Sensor Images

Inquiry Cart 0
Send your message to this supplier
 
*From:
*To: Nanjing Juge Environmental Technology Co., Ltd.
*Subject:
*Message:
Characters Remaining: (0/3000)